Please provide feedback on the quote provided.We are always willing to work with you on pricing
Product Details:
F3330: 8 fold output module, safety related resistive load or inductive load up to 500 mA (12 W),
lamp connection up to 4 W, with integrated safety shutdown, with safe isolation,
no output signal with break of the L- supply requirement class AK 1 … 6
The module is automatically tested during operation. The main test routines are: – Reading back of the output signals.
The operating point of the 0 signal read back is ≤ 6.5 V. Up to this value the level of the 0 signal may arise
in case of a fault and this will not be detected – Switching capability of test signal and cross-talking (walking-bit test).
- Outputs 500 mA, k short circuit proof
- Internal voltage drop max. 2 V at 500 mA load
- Admissible line resistance (in + out) max. 11 Ohm
- Undervoltage tripping at ≤ 16 V
- Operating point for short circuit current 0.75 … 1.5 A
- Outp. leakage current max. 350 µA
- Output voltage if output is reset max. 1,5 V
- Duration of the test signal max. 200 µs
- Space requirement 4 TE
- Operating data 5 V DC: 110 mA
- 24 V DC: 180 mA in add. load
- HIMA F3331 Output Module
HIMA F3406 Relay Module
HIMA F4101 Control Module
HIMA F4201 Control Module
HIMA F6203 Counter Module
HIMA F7102 Insulation Monitor Module
HIMA F7511 Control Module
HIMA F8201 Control Module
HIMA F8621/A CPU Module
HIMA F6220 Process Module
HIMA F8601 Control Module Card
HIMA F8620/11 Central Processing Unit
HIMA F8640 CPU Module
HIMA ZBT-F 9402 Series 8250 Cardfile
HIMA F8652X Safety-Related CPU
HIMA H4135 992413502 Safety Relay
HIMA H4135A 992413560 Safety Relay
There are no reviews yet.