About FAQ
Q1: How long is your delivery time?
A1: If the goods are in stock,it usually takes 2-3 working days.If the quantity is large,
it will take 5-7 working days after receiving the payment.
Q2. What about your shipping package?
A2.Most of our products is ship with original factory new package, we will cover our
our professional foam protective packaging to keep worldwide shipping no dama
Q3. How is the quality of your products? How long is the warranty period?
A3.We guarantee that the products provided are original products of,and the warranty period of all products is 12 months.
Our company
Xingruijia limited always make the best staff and spare parts together,professional multilingual service team,
adhere to provide customers with first-class service.Company products covers DCS control system card,
programmable PLC module SPS/CNC panel controller/inverter/server driver and various parts
of the robot.Whether it is a new spare parts, or outdated/discontinued parts,Moore is committed to
the best cost, best quality and efficient way to allow enterprises to resume normal
Product:Digital Output Triconex DCS TRICONEX Invensys MP3101 For Critical Control Digital 24VDC Output Module
Designed for the most critical control programs, Supervised Digital Output (SDO) modules meet the needs of systems whose outputs remain in a single state for extended periods of time (in some applications, for years). An SDO module receives output signals from the Main Processors on each of three channels. Each set of three signals is then voted upon by a fully faulttolerant quadruplicated output switch whose elements are power transistors, so that one voted output signal is passed to the field termination.
Each SDO module has voltage and current loopback circuitry coupled with sophisticated online diagnostics that verify the operation of each output switch, the field circuit and the presence of a load. This design provides complete fault coverage without the need to influence the output signal.
The modules are called “supervised” because fault coverage is extended to include potential field problems. In other words, the field circuit is supervised by the SDO module so that the following field faults can be detected:
• Loss of power or blown fuse
• Open or missing load
• A field short resulting in the load being energized in error
• A shorted load in the de-energized state