sales1@xrjdcs.com+86 15359273791
Welcome to our websites!

TRICONEX CM3201 Communication Module

In stock

Place of Origin USA
Brand Name TRICONEX
Model Number MP3101
Minimum Order Quantity 1pc
Price $5000
Packaging Details New and original factory, individual box packing
Delivery Time 5-7days
Payment Terms T/T
Supply Ability 9pcs

Click here for good price 

Brand/Manufacturer   TRICONEX /USA
Part Number CM3201
Warranty   12 months
Description   Communication Module
Dimennsions   29x26x20cm 
Weight   4.37 kg

FAQ

1.Q: Does your goods are new and original?

A: yes,they are new and original.

2.Q: Could provide technology support?

A: Were in this field more than 12 years with a professional technical team to serve our customers.

3.Q:Dose keeps goods in stock?

A: We have large warehouse for goods,keep lots of goods in warehouse,so could promise fast delivery.

4.Q:Can you provider discount?

A: Yes,we are glad to offer you discount if you order more piece.

5.Q: What about your lead time?

A: We hanve many items in stock,3-5 days you will receive it.

6.Q: Dose test the products before shipping?

A: Yes,we have professional technology staff to test the goods before.

Product:Digital Output Triconex DCS TRICONEX Invensys MP3101 For Critical Control Digital 24VDC Output Module

Designed for the most critical control programs, Supervised Digital Output (SDO) modules meet the needs of systems whose outputs remain in a single state for extended periods of time (in some applications, for years). An SDO module receives output signals from the Main Processors on each of three channels. Each set of three signals is then voted upon by a fully faulttolerant quadruplicated output switch whose elements are power transistors, so that one voted output signal is passed to the field termination.

Each SDO module has voltage and current loopback circuitry coupled with sophisticated online diagnostics that verify the operation of each output switch, the field circuit and the presence of a load. This design provides complete fault coverage without the need to influence the output signal.

The modules are called “supervised” because fault coverage is extended to include potential field problems. In other words, the field circuit is supervised by the SDO module so that the following field faults can be detected:

• Loss of power or blown fuse

• Open or missing load

• A field short resulting in the load being energized in error

• A shorted load in the de-energized state

Welcome to contact me:

Sales manager:Jinny

Email:sales1@xrjdcs.com

Skype:xrjgk@hotmail.com

Whatsapp/Mobile: + 86-15359273791

We can offer the best price in the market!

    Customers reviews

    There are no reviews yet.

    Be the first to review “TRICONEX CM3201 Communication Module”

    Your email address will not be published. Required fields are marked *